Your current location: ProductsPower Station ValveEmpty Drain Check Valve

H48Y/H Empty Drain Check Valve

Product overview

Product model: H48Y (H)
Nominal diameter: DN50 ~ 250mm
Nominal pressure: PN20MPa
Operating temperature: ≤160℃
Design and Manufacture: ASME B16.34, JB/T3595, E101
Pressure and temperature: ANSI B1 6.34, JB/T74, JB/T3595, E101
Structure length: ANSI B16.10, E101, GB/T15188.1, JB/T2766
Butt welding connection size: ASME B16.25, GB/T12224, E101
Inspection and test: ISO5208, GB/T13927, JB/T3595

H48Y/H Empty Drain Check Valve product details

H48Y/H Empty Drain Check Valve overview

H48Y/H Empty Drain Check Valve produced and sold by Baigang valve group installed in the thermal power unit to the large pump outlet pipe to prevent water back to protect the pump. The valve with the minimum flow pump automatically recirculation next to the valve work, when the pump in the low load or outlet cut-off state, the automatic recirculation bypass valve should be in the open position to ensure the safe operation of the pump. When empty check valve opens, the recirculation bypass valve closes automatically. Should not be used for containing solid particles and larger viscosity media.


H48Y/H Empty Drain Check Valve structure features

As a principle: Open the outlet valve, start the pump, water reaches a certain pressure, the valve pressure in the water under the role of a certain height, pushed off the valve seat, the water that is out. At the same time due to the valve flap rise, drive connecting rod rotation, toggle the exhaust port valve, the recirculation blade valve to move down, close the exhaust port. When the water flow decreases, the valve flap down, push the connecting rod to open the emptying valve, open the recycling door to maintain the pump's minimum allowable flow. When the pump is stopped, the valve flap will automatically fall off and the valve port passage will be closed to prevent the damage of the high pressure water hammer water supply system.

Structural features: The valve with the recycling bypass valve work to maintain the safe operation of the system. The main valve flap moves up and down. When the media is flowing backwards, the bypass valve is closed by means of medium pressure and spring. At this time, the bypass valve is opened. When the main valve flap is fully open, the bypass valve is closed. Valve seal made of stainless steel surfacing, wear-resistant, abrasion resistance, reliable sealing. The valve should be installed vertically.


H48Y/H Empty Drain Check Valve main parts and materials 

Part Name

material

Body, connecting flange, exhaust flange, flange cover

Carbon steel

Shaft, fork, sleeve, slider, exhaust sleeve, exhaust disc

stainless steel

Valve, valve body, valve shaft, connecting fork

High-quality carbon steel

bushing

Cast aluminum bronze

Bolts and nuts

High-quality carbon steel


H48Y/H Empty Drain Check Valve main connection size  

DN

L

D

D1

D2

D6

b

Zd

f

f2

H

Weight (kg)

100

430

360

292

245

138

66

8-41

3

6

630

285

150

550

440

360

305

190

82

12-Ф48

3

6

650

510

175

610

475

3944

340

214

84

12-Ф48

3

6

685

700

225

900

580

483

418

268

100

12-Ф58

3

6

765

1105

250

900

670

572

508

319

110

16-Ф58

3

6

780

1330